ABB i-bus
KNX
Commissioning
The parameter is used to set when the value of the internal brightness sensor is to be sent.
Never: Sending on the bus is deactivated.
On request: The 1-bit object Bus request to send lux – Reception is activated. The measured lux
value is sent on the bus via the corresponding object when the "On" value is received on this object.
On request and automatically/cyclically: The 1-bit object Bus request to send lux – Reception is
activated. The measured lux value is sent on the bus via the corresponding object when the "On"
value is received on this object. The dependent parameter Sending cycle for measurement value is
additionally activated.
On request and change: The 1-bit object Bus request to send lux – Reception is activated. The
measured lux value is sent on the bus via the corresponding object when the "On" value is received
on this object. The dependent parameter Send at percentage change in measurement value is
additionally activated.
On request, change and automatically/cyclically: The 1-bit object Bus request to send lux – Reception
is activated. The measured lux value is sent on the bus via the corresponding object when the "On"
value is received on this object. The dependent parameters Sending cycle for measurement value
and Send at percentage change in measurement value are additionally activated.
Sending cycle for measurement value
Options:
Every 30 seconds
Every minute
Every hour
Every 6 hours
Every 12 hours
At midnight
At 00:02
Depending on the selection, the measured lux value is correspondingly sent cyclically on the bus.
Send at percentage change in measurement value
Options: 1 ... 10 ... 50
The value set here determines the percentage change in the measurement value at which the new
value is to be sent on the bus.