ABB i-bus
KNX
Commissioning
Reaction on removing the block
Options:
Send current value
No action
The parameter defines the temperature control reaction when the block is canceled.
Send current value: The currently valid temperature control value is sent.
No action: The object does not send its current status automatically, but only after the
next change.
Reaction on setting the block
Options:
No action
Send a telegram
The parameter defines the temperature control reaction when the block is set.
No action: The object does not send anything and is blocked.
Send a telegram: A telegram is sent on the bus via the object Sends temperature
above/below setpoint temperature – Sending or Sends scene temperature above/below
setpoint temperature – Sending when the block is set. The dependent parameter
Telegram on setting the block is enabled.
Telegram on setting the block
The parameter options depend on the selected Switching bit or Scene parameter.
The following options are available if Switching bit was selected:
Options:
0: The value 0 is sent.
1: The value 1 is sent.
The following values are available if Scene was selected:
Options:
The selected scene number is sent on the bus when the block is activated.
0
1
1 ... 64
TR/A 1.1 | 2CDC509082D0201 63