KNX
Commissioning
The parameter is used to set when the value of the internal temperature sensor is to be sent.
Never: Sending on the bus is deactivated.
On request: The 1-bit object Bus request to send temperature – Reception is activated.
The measured temperature is sent on the bus via the corresponding object when the "On" value is
received on this object.
On request and automatically/cyclically: The 1-bit object Bus request to send temperature –
Reception is activated. The measured temperature value is sent on the bus via the corresponding
object when the "On" value is received on this object. The dependent parameter Sending cycle for
measurement value is additionally activated.
On request and change: The 1-bit object Bus request to send temperature – Reception is activated.
The measured temperature value is sent on the bus via the corresponding object when the "On"
value is received on this object. The dependent parameter Send on measurement value change in
[0.1°C] is additionally activated.
On request, change and automatically/cyclically: The 1-bit object Bus request to send temperature –
Reception is activated. The measured temperature is sent on the bus via the corresponding object
when the "On" value is received on this object. The dependent parameters Sending cycle for
measurement value and Send on measurement value change in [0.1°C] are additionally activated.
Sending cycle for measurement value
Options:
Every 30 seconds
Every minute
Every hour
Every 6 hours
Every 12 hours
At midnight
At 00:02
Depending on the selection, the measured temperature value is correspondingly set cyclically on
the bus.
Send on measurement value change in [0.1°C]
Options: 1 ... 10 ... 255
The value set here determines the change in the measurement value at which the new value is to
be sent on the bus. The value is specified in increments of 0.1 °C; entering the value 10 causes the
measurement value to be sent each time it changes by 1 °C.