ABB i-bus KNX Product Manual page 62

Time receiver gps, tr/a 1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
60 2CDC509082D0201 | TR/A 1.1
Delay temperature setpoint in [s]
Options:
0 ... 60 ... 3,600
A delay for evaluating the actual temperature with the setpoint temperature can be set in this
parameter. This permits compensation for brief fluctuations, e.g. when the sun appears briefly
through the cloud cover on a heavily overcast day. The time set here leads to switchover
occurring only when the outside value is above/below the setpoint for the set time.
Temperature logic
Options:
T < setpoint (heating)
T > setpoint (cooling)
The temperature control function is set with this parameter. Depending on the selection, the
output object Sends temperature above/below setpoint temperature – Sending is switched from 0
to 1 when the value exceeds the setpoint temperature (T < setpoint (heating)) or falls below the
setpoint temperature (T > setpoint (cooling)). The switch-on/switch-off value is sent analogously if
a scene object instead of a switching bit is used as the output object.
The measured temperature (or the temperature received via the object) is constantly compared
with the setpoint to determine the switchover time.