ABB i-bus
KNX
Commissioning
Switch ON
Options:
Inactive
Active
An additional "On" period can be activated for time switch Astro Plus with this parameter. An "On"
signal is additionally sent via the output object of the time switch during this period, e.g. to switch on
lighting additionally during a certain period.
•
Inactive: The additional "ON" period is deactivated.
•
Active: The following parameters are displayed.
Switch on from [hour]
Option:
0 ... 18 ... 23
The hour of the switch-on time is defined with this parameter. The scene value or the corresponding
switching-bit value defined for "On" will be sent at this time.
Switch on from [minute]
Option:
0 ... 59
The minute of the switch-on time is defined with this parameter. The scene value or the
corresponding switching-bit value defined for "On" will be sent at this time.
Switch on to [hour]
Option:
0 ... 6 ... 23
The hour of the switch-on time is defined with this parameter. The scene value or the corresponding
switching-bit value defined for "Off" will be sent at this time.
Switch on to [minute]
Option:
0 ... 59
The minute of the switch-on time is defined with this parameter. The scene value or the
corresponding switching-bit value defined for "Off" will be sent at this time.
TR/A 1.1 | 2CDC509082D0201 55