ABB i-bus KNX Product Manual page 72

Time receiver gps, tr/a 1.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
18
The group object is enabled if the Send sunrise and sunset times parameter is set to On request or On request and
automatically/cyclically in the GPS coordinates and sun data – GPS sun data parameter window.
The object is used to trigger sending of the sunrise and sunset times on the bus.
19
The group object is enabled if the Send measurement value parameter is set to On request, On request and
automatically/cyclically, On request and change or On request, change and automatically/cyclically in the Temperature –
Temperature sensor parameter window.
The object is used to send the current outside temperature measured by the temperature sensor on the KNX bus.
20
The group object is enabled if the Send measurement value parameter is set to On request, On request and
automatically/cyclically, On request and change or On request, change and automatically/cyclically in the Light – Light sensor
parameter window.
The object is used to send the current brightness value measured by the brightness sensor on the KNX bus.
21
The group object is enabled if the Send measurement value parameter is set to On request, On request and
automatically/cyclically, On request and change or On request, change and automatically/cyclically in the Temperature –
Temperature sensor parameter window.
The object is used to trigger sending of the current temperature value on the bus.
22
The group object is enabled if the Send measurement value parameter is set to On request, On request and
automatically/cyclically, On request and change or On request, change and automatically/cyclically in the Light – Light sensor
parameter window.
The object is used to trigger sending of the current brightness value on the bus.
70 2CDC509082D0201 | TR/A 1.1
Reception
Sending
Sending
Reception
Reception
Bus request to send sun
times – Reception
Sends the temperature on the
bus – Sending
Sends the light value on the
bus – Sending
Bus request to send the
temperature – Reception
Bus request to send the lux
value – Reception
1-bit
C, W
DPT 1.017
2-byte
C, T
DPT 9.001
2-byte
C, T
DPT 9.004
1-bit
C, W
DPT 1.017
1-bit
C, W
DPT 1.017

Advertisement

Table of Contents
loading

Table of Contents