IP 266
Input currents
5 V
24 V
Digital inputs
Input voltage range
Galvanic isolation
0 signal
1 signal
Permissible quiescent current for 0 signal
Typ. input current at 24 V
Digital outputs
Output voltage range
Galvanic isolation
Max. output current for "1" signal
Short-circuit protection
Length of shielded cable
Supply voltage
Logic voltage generated from ext. 24 V
with switched-mode power supply
Power input from 24 V
without outputs and 24 V encoder
EWA 4NEB 812 6057-02
Technical Description of the IP 266
Electrical Specifications
: to RS 422
: 7.3 mA typ.
: ±30 V
: No
: - 30 V to+5 V
: 13 V to 30 V
: 1.5 mA
: 7.3 mA
: 20 V to 30 V
: no
: 100 mA
: Short-circuit-proof output
: Max. 100 m
: 4.7 V to 5.5 V
: 180 mA typ.
2-27