4.4 Jumper Links for Relay Outputs –
CM15 Indicator
The factory-set default for relay action is N/O.

4.4.1 Removing the CM15 Indicator from its Case

The indicator's inner assembly must be removed from its
case to access the relay contact jumper links.
Referring to Fig. 4.10:
1. Insert the bezel release tool
B
panel slot
to the left of the function keys.
2. Press the bezel release tool
until the shoulder on the tool engages with the notch
behind the indicator front plate.
3. Pull the bezel release tool
assembly from the case
Note. If the bezel release tool is mislaid, 2 small
flat-headed screwdrivers (4 mm [0.15 in.]) can be used as
alternative tools, one inserted into the front panel slot and
the second for leverage in the notch behind the indicator
front plate. The notch is the only area that can be used as
a leverage point – do not attempt to lever the front panel
from any other area.