ControlMaster CM15 and CMF160
Universal process indicator
...Functions / ...Bank Control
Bank Size
Control Source
Stage 1 (6)
Off Trip
On Trip
Output
Schedule
74
1
/
DIN
8
Select the number of stages (pumps) required for the application from 2 to 6 or Off.
Off disables the Bank Control functionality.
Select the analog signal to act as the control signal for the bank control.
This is normally the Process Variable (PV) for most pump control applications.
Select the Control Source value (PV) at which the output (pump) is turned off.
Select the Control Source value (PV) at which the output (pump) is turned on.
Select the initial output (relay or digital output) that the output is assigned to by
default (for example, when FIFO or Rotate mode is not in operation).
Select the wear levelling schedule required:
Off – the output is not controlled by the bank schedule.
The state of the output is controlled entirely by its associated trip points.
FIFO – the output is controlled according to the FIFO schedule mode.
Rotate – the output is controlled according to the Rotate schedule mode.
7 Advanced Level
IM/CM/I–EN Rev. P