ABB ControlMaster CM15 User Manual page 81

Universal process indicator / din and fieldmount
Hide thumbs Also See for ControlMaster CM15:
Table of Contents

Advertisement

ControlMaster CM15 and CMF160
Universal process indicator
Number /
Icon
Possible Cause
Message
F212.018
Failure of non-volatile memory on option board 1 or
NV Error Opt Bd 1
permanent corruption of its data.
F210.019
Failure of non-volatile memory on option board 2 or
NV Error Opt Bd 2
permanent corruption of its data.
F208.020
Failure of non-volatile memory on communications board
NV Error
or permanent corruption of its data.
Comm Bd
F206.021
Failure of non-volatile memory on Software key 1 or
NV Error SW
permanent corruption of its data.
Key 1
F204.022
Failure of non-volatile memory on Software key 1 or
NV Error SW
permanent corruption of its data.
Key 2
Table 7.1 Diagnostic Messages (Continued)
IM/CM/I–EN Rev. P
1
/
DIN
8
Suggested Action
Check calibration of AIN1 and AIN2.
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service organization.
Check calibration of AIN3 and AIN4.
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service organization.
Acknowledge error. Check communications board is
correctly identified by device.
If problem persists contact local service organization.
Acknowledge error.
Check software key functionality is enabled.
If problem persists contact local service organization.
Acknowledge error.
Check software key functionality is enabled.
If problem persists contact local service organization.
7 Advanced Level