ControlMaster CM15 and CMF160
Universal process indicator
... Input/Output / ...Analog Input 1 (4)
Elect. Low
Elect. High
Linearizer
IM/CM/I–EN Rev. P
1
/
DIN
8
Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Ohms.
Linear Inputs
Reading)
Millivolts
Milliamps
Volts
Resistance  (low)
Resistance  (high)
Sets the required electrical range.
Note. Applicable only to Millivolts, Milliamps, Volts and Freq. Input.
Selects the linearizer type required to condition the input signal.
Notes. For thermocouple applications using an external fixed cold junction, set Input
Type to Millivolts (see page 44) and select the appropriate linearizer type.
Not applicable for Pulse Input, Digital volt-free, 24V Digital parameters – see page 44.
Standard Analog Input
0 to 150 mV
0 to 45 mA
0 to 25 V
0 to 550 
0 to 10 k
7 Advanced Level
Accuracy (% of
0.1 % or ±20 µV
0.2 % or ±10 µA
0.2 % or ±20 mV
0.2 % or ±1 
0.1 % or ±5 