ABB ControlMaster CM15 User Manual page 92

Universal process indicator / din and fieldmount
Hide thumbs Also See for ControlMaster CM15:
Table of Contents

Advertisement

ControlMaster CM15 and CMF160
Universal process indicator
Outputs
Retransmission outputs
Number
CM15: 2 (1 standard, 1 optional)
CMF160: 4 (2 standard, 2 optional)
Isolation
Galvanically isolated from the rest of the circuitry,
500 V for 1 minute
Analog range
0 to 20 mA programmable
750  max.
Load
Accuracy
0.25 % of output or ±10 µA
Relays
Number
CM15: 4 (1 standard, 3 optional)
CMF160: 6 (4 standard, 2 optional)
Type
Standard with changeover contacts
CM15 only – optional contacts selectable
as NO or NC (by jumper)
CM15: relay 1 contact rating
CM15: relay 2, 3 and 4 contact
ratings at maximum ambient
temperature of 40 °C (104 °F)
CM15: relay 2, 3 and 4 contact
ratings at maximum ambient
temperature of 55 °C (131 °F)
CMF160: contact ratings
Update rate
90
1
/
DIN
8
5 A, 240 V
5 A, 240 V
2 A, 240 V
2A 240 V
125 ms
Digital I/O
Number
CM15: 2 (optional)
CMF160: 6 (standard)
Type
User-programmable as input or output
Minimum input pulse duration – 125 ms
Input
Volt-free
contact open > 10 M /
contact closed < 100 k
24 V DC
1-signal 15 to 30 V / 0-signal –3 to 5 V
TTL
low: 0 to 0.8 V / high: 2 to 5 V
Conforms to IEC 61131-2
Output
Open collector output
30 V, 100 mA max. switched
Conforms to IEC 61131-2
Update rate
125 ms
2-Wire transmitter power supply
Number
CM15: 1 (standard)
CMF160: 1 (optional)
Voltage
24 V DC
Drive
2 loops, 45 mA max.
10 Specification
IM/CM/I–EN Rev. P

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Controlmaster cmf160

Table of Contents