ControlMaster CM15 and CMF160
Universal process indicator
7.5 Totalizer
Two 9-digit totalizers are provided. These can be configured independently to totalize any analog or digital
Menu
Totalizer
signal. Four modes of operation are provided.
Where possible, the count rate is calculated automatically according to source units, totalizer units and
engineering range.
Totalizer 1 (2)
Mode
Off
Analog
Digital
Frequency
Pulse
Source
54
1
/
DIN
8
Totalizer disabled.
Totalization of any analog signal.
Counting of low / high transitions of any digital signal (for example, digital input or alarm) minimum
pulse duration >125 ms.
Totalization of a frequency input on Analog input 1.
Totalization of a pulse input on Analog input 1.
The input to be totalized. The inputs available for selection are dependent on the
Not displayed for frequency and pulse inputs – see Appendix A, page 94 for description of
sources.
7 Advanced Level
selected.
Mode
IM/CM/I–EN Rev. P