ABB ControlMaster CM15 User Manual page 91

Universal process indicator / din and fieldmount
Hide thumbs Also See for ControlMaster CM15:
Table of Contents

Advertisement

ControlMaster CM15 and CMF160
Universal process indicator
Inputs
Thermocouple
Maximum range °C (°F)
B
–18 to 1800
(0 to 3270)
E
–100 to 900
(–140 to 1650)
J
–100 to 900
(–140 to 1650)
K
–100 to 1300
(–140 to 2350)
L
–100 to 900
(–140 to 1650)
N
–200 to 1300
(–325 to 2350)
R
–18 to 1700
(0 to 3000)
S
–18 to 1700
(0 to 3000)
T
–250 to 300
(–400 to 550)
* Accuracy is not guaranteed at temperatures below this value
RTD
Maximum range °C (°F)
Pt100
–200 to 600
(–325 to 1100)
IM/CM/I–EN Rev. P
1
/
DIN
8
Accuracy (% of reading)
0.1 % or ±2 °C (3.6 °F)
(above 200 °C [392 °F]) *
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±1.5 °C (2.7 °F)
0.1 % or ±0.5 °C (0.9 °F)
0.1 % or ±1 °C (1.8 °F)
(above 300 °C [540 °F]) *
0.1 % or ±1 °C (1.8 °F)
(above 200 °C [392 °F]) *
0.1 % or ±0.5 °C (0.9 °F)
(above –150 °C [–238 °F]) *
Accuracy (% of reading)
0.1 % or ±0.5 °C (0.9 °F)
Linear inputs
Standard analog input
Millivolts
0 to 150 mV
Milliamps
0 to 45 mA
Volts
0 to 25 V
0 to 550 
Resistance (low)
Resistance (high)
0 to 10 k
Sample Interval
125 ms per sample
Digital inputs
Type
Volt-free or 24 V
Minimum pulse
Single input configured – 250 ms
duration
Both inputs configured as analog or digital – 500 ms
Volt-free
Contact open > 10 M / contact closed < 100 k
Frequency input*
Frequency range
0 to 6000 Hz
1-signal
15 to 30 V
0-signal
–3 to 5 V
* For use with devices with open collector outputs
10 Specification
Accuracy (% of reading)
0.1 % or ±20 µV
0.2 % or ±4 µA
0.2 % or ±20 mV
0.2 % or ±0.1
0.1 % or ±10
89

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Controlmaster cmf160