7.8.1 Diagnostic Messages

Number /
Icon
Possible Cause
Message
Problem with Input assigned to Loop 1 (2) PV. Broken
F250.00
sensor leads, defective input source or input signal out of
PV 1 Failed
permitted range.
Problem with Input assigned to Loop 1 (2) PV. Broken
F248.001
sensor leads, defective input source or input signal out of
PV 2 Failed
permitted range.
F222.014
Error in Cold junction measurement associated with AIN1
CJ 1 Failed
(AIN3). Wiring fault or defective sensor.
F220.015
Error in Cold junction measurement associated with AIN1
CJ 2 Failed
(AIN3). Wiring fault or defective sensor.
F216.016
Failure of non-volatile memory on processor display
NV Error Proc Bd
board or permanent corruption of its data.
F214.017
Failure of non-volatile memory on main board or
NV Error Main Bd
permanent corruption of its data.
Table 7.1 Diagnostic Messages
78
1
/
DIN
8
Suggested Action
Check wiring. Check input source. Check if input signal is
outside permitted limits.
Check wiring. Check input source. Check if input signal is
outside permitted limits.
Check cold junction device is correctly fitted. Ensure I/P 2
is turned off. Replace CJ sensor.
Check cold junction device is correctly fitted. Replace CJ
sensor.
Check all configuration parameters and correct any errors.
Acknowledge error. If problem persists contact local
service organization.
Check calibration of AO1 and AO2.
Recalibrate if necessary. Acknowledge error.
If problem persists contact local service organization.