Systems With ³5 M (³18 Ft) Cable Length - ABB Endura AZ series User Manual

Integral and remote transmitter, combustion oxygen monitor
Table of Contents

Advertisement

Endura AZ series integral and remote transmitter
Combustion oxygen monitor
4.4.2 Systems with 5 m (18 ft) Cable Length
Sensor connection
White / Yellow (not used)
White / Black (not used)
White / Orange (not used)
White / Green (not used)
White / Red (not used)
White / Blue (not used)
Red
Black
Violet
Grey
Green
White
Earth stud (Screen 1 and 2)
Brown
Blue
Table 4.2 Systems with
Signal connections
Not used – see Table 4.2
H (Brown) H (Blue)
Special ABB 14-core Cable Only:
5 m (
18 ft) Length
Fig. 4.5 Systems with
5 m (
16
Transmitter Connection
White / Yellow (not used)
White / Black (not used)
White / Orange (not used)
White / Green (not used)
White / Red (not used)
White / Blue (not used)
Red
Black
Violet
Grey
Green
White
SCN (Screen 1 and 2)
Brown
Blue
5 m (
18 ft) Cable Length
AZ10 remote transmitter
18 ft) Cable Length
Cable Color
White / Yellow (not used)
White / Black (not used)
White / Orange (not used)
White / Green (not used)
White / Red (not used)
White / Blue (not used)
Red
Black
Violet
Grey
Green
White
Screen 1 and 2 (sleeved drains)
Brown
Blue
AZ10 sensor
Green (earth wire from
sensor earth stud)
CLR
W BL
R
CLR
+
– +
T/C
H1 H2
+
+
ACJC
H1
H2
T/C
CELL
Screen 1 and 2 drains at sensor
connected to internal earth stud only
Screen 1 and 2 drains insulated from transmitter
case and connected to SCN terminal connection
only – not via gland or case
4 Electrical Installation
Connection / Note
NOT USED
Cut wires back at
both ends of cable
Cell + (oxygen input)
Cell – (oxygen input)
ACJC
ACJC
T/C +
T/C –
See Fig.
4.5
Heater 1
Heater 2
H (Blue) H (Brown)
Cell + (Red)
Cell – (Black)
ACJC (Violet)
ACJC (Grey)
T/C + (Green)
T/C – (White)
SCN (Screen) –
Screen 1 and 2
drains
IM/AZ20E–EN Rev. F