ABB Endura AZ series User Manual page 43

Integral and remote transmitter, combustion oxygen monitor
Table of Contents

Advertisement

Endura AZ series integral and remote transmitter
Combustion oxygen monitor
Parameter
...Calibrate
...Scheduled Cal.
Time of Next Cal.
Sequence
Calibration
Accuracy check
Cal. On Error limit
Warn On Error Limit
Cal. Error Limit
Table 5.7 Calibrate Menu (Continued)
IM/AZ20E–EN Rev. F
Comment / [Range]
If AutoCal is fitted, calibrations can be set to run
automatically at scheduled time intervals.
Note. This option is not available if the AutoCal
Hardware / Hardware Type is set to None.
Selects the time and date of the next and subsequent
scheduled calibrations. No scheduled calibrations are
performed until the date / time set is reached. The date
of
the
next
scheduled
automatically according to the frequency set. For
example, if Frequency is 5 days and Time of Next Cal. is
12:00:00 2009-01-05, it is updated automatically to
12:00:00 2009-01-10.
Note. If the scheduled calibration cannot be run, or is
unsuccessful, the next scheduled calibration date is
updated according to the frequency set and an Out of
Specification / Missed Scheduled AutoCal diagnostic
message is created – see Section 8.2.2, page 82.
Selects the type of calibration / check to be performed.
Performs a calibration that automatically updates the
calibration offset and factor if successful.
Performs an accuracy check – this follows the normal
calibration sequence, but does not update the
calibration offset and factor in use by the transmitter.
Performs an accuracy check but if the error is greater
than the set Cal. Error Limit (see below), the calibration
offset and factor are updated automatically.
Performs an accuracy check, but if the error is greater
than the Cal. Error Limit value, a calibration required
warning is generated.
Sets the limit for use with Warn On Error Limit field.
[0.01 to 10.00 % O
]
2
calibration
is
updated
5 Programming
Default
N / A
Calibration
1.00 % O
2
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Endura az25Endura az20Endura az10

Table of Contents