Endura AZ series integral and remote transmitter
Combustion oxygen monitor
Parameter
...Device Setup
Oxygen Setup
%O2 Range Hi
%O2 Range Lo
Filter Time
Pressure Comp.
Temp. Setup
Thermocouple Type
K
B
N
R
S
Temperature Units
Table 5.9 Device Setup Menu (Continued)
46
Comment / [Range]
Sets the maximum oxygen concentration
[0.01 to 100 % O
]
2
Sets the minimum oxygen concentration
[0.01 to 100 % O
]
2
Sets the amount of filtering time required on the oxygen
input measurement.
Note. This is a rolling-average filter.
[1 to 60 s]
Sets the pressure compensation value.
Note. Set a value if, in normal operation, positive or
negative pressure with respect to the pressure during a
calibration is present. If calibrations are performed at the
same pressure as normal operation, set this value to
0.00 psi.
[– 5.00 to 5.00 psi]
Selects thermocouple type and temperature units.
Selects the thermocouple type used for cell temperature
measurement.
For heated probes (AZ20 and AZ30) this is fixed as type K.
For unheated probes (AZ25 and AZ35), select the
thermocouple type used in the probe.
[–100 to 1300 °C (–148 to 2372 °F)]
[–18 to 1800 °C (–0.4 to 3272 °F)]
[–200 to 1300 °C (–328 to 2372 °F)]
[–18 to 1700 °C (–0.4 to 3092 °F)]
[–18 to 1700 °C (–0.4 to 3092 °F)]
Selects the temperature units to be used in the
transmitter.
5 Programming
Default
25.00 %O
2
0.01 %O
2
1 s
0.00 psi
K
°C
IM/AZ20E–EN Rev. F