Endura AZ series integral and remote transmitter
Combustion oxygen monitor
Command
Description
No.
12
Read Message
13
Read Tag, Descriptor
and Date
14
Read Primary Variable
Sensor Information
15
Read Primary Variable
Output Information
16
Read Final Assembly
Number
17
Write Message
18
Write Tag, Descriptor
and Date
19
Write Final Assembly
Number
Table 7.2 HART Universal Commands Set (Continued)
IM/AZ20E–EN Rev. F
Details
Returns the user-defined HART message.
Message can also be viewed via Communications menu on
the transmitter's local HMI.
Returns the user-defined HART information:
HART Tag
HART Descriptor
device installation date
Returns the range limits and minimum permissible span for
the probe.
PV Alarm selection code:
0 = Low,
1 = High,
239 = Hold Last Output Value.
PV upper and lower range values.
Filter (damping) time.
HART write protection code.
Any private label distributor code associated with the
transmitter.
Returns the user-defined final assembly number. Number can
also be viewed via Communications menu on the device's
local HMI.
Enables a user-defined message of up to 32 characters to be
entered.
Message
Communications menu on the device's local HMI.
Enables the user to assign a user-defined 8-character tag to
the transmitter.
Enables a user-defined 16-character descriptor to be entered.
Allows an installation date to be entered.
Enables a user-defined final assembly number to be entered.
This can be used for inventory or maintenance purposes.
7 HART®-Protocol
can
also
be
entered
via
the
71