4.2.4.2
Configuring the transmission rate and CAN bus address
Note
• Permissible CAN bus addresses are 1...127.
• Each change using the address switch p8620 or in the screen form is not effective until
POWER ON.
• While the SINAMICS is being booted, the address switch is queried first in order to set
the bus address. If this is set to 0, the address can be set using parameter p8620.
• If the address is set to a valid node address (1...127), this is copied to parameter p8620,
where it is displayed.
• The value in p8620 or in the screen form is written with the STARTER download.
CANopen interface
Commissioning Manual, 11/2017, 6SL3097-4AA00-0BP3
4.2 Configuring the CANopen interface
Configuration