Procedure
To restore the factory settings, proceed as follows:
1. Open the "Online & diagnostics" entry at "Online access".
2. Open the entry "Functions" in the secondary navigation.
3. Double-click the "Restore factory settings" entry in the secondary navigation.
The dialog box with the current settings is displayed.
Figure 4-57
4. Click the "Reset" button.
The drive communication settings are reset to the factory settings.
5. Go offline and then establish an online connection again. The factory settings of the IP
address and the device name are now displayed at "Online access".
Result
The communication settings show the factory settings again.
Note
After the reset, it makes sense to then assign an IP address and a device name to the drive,
also refer to Chapter "Assigning an IP address (Page 143)" and "Assigning PROFINET
device names (Page 145)".
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Restoring factory settings
4.5 Establishing an online connection to the drive unit