Commissioning
4.7 Basic parameterization of the drive objects
4.7.4.5

Drive settings

No entries are required on this page for motors with DRIVE-CLiQ interface or motors of the
motor database.
Figure 4-83
Setting the automatic calculation of motor/control parameters
1. Select one of the following applications in the "Technology application" (p0500) drop-
down list:
– Standard drive (VECTOR)
– Pumps and fans
– Encoderless control down to f = 0 (passive loads)
– Dynamic response in the field weakening range
– Approach with high break loose torque
– High load inertia
2. In the drop-down list "Motor data identification and rotating measurement" (p1900), select
how the motor data identification is to be carried out for a stopped motor:
– Inhibited
– Motor data ident. (standstill) and speed controller opt.
– Identify motor data (standstill)
– Optimize the speed controller (rotating)
194
Drive settings
With this setting, the drive is run up to speed upon 2nd actuation.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1