Siemens SINAMICS S120 Commissioning Manual page 211

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Activating the infeed
If an infeed is available in your drive, then the infeed must also be activated. If it is not
activated, no further drive release can be set.
1. Click the "1" icon at "Infeed" to switch on the infeed.
Deactivating the control panel
When you deactivate the control panel, you return the master control.
To deactivate the control panel, proceed as follows:
1. Click the "Off" button to switch off the drive.
This is a basic requirement for deactivating the control panel.
2. Click "Deactivate" at "Master control".
The grayed-out user interface of the control panel shows that the master control has been
deactivated.
Setting the enable
To set the required enable for the control panel, proceed as follows.
1. Click "Set" at "Drive enables".
Further areas of the control panel are activated.
2. Click "Acknowledge faults" to acknowledge the currently pending faults.
3. If you no longer require the enables, click "Reset" at "Drive enables".
Result
You can now traverse the drive with the control panel. Enables and faults are displayed at
"Drive status". In addition to "Active fault", the currently pending fault is displayed.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Commissioning
4.9 Commissioning a drive
211