Line Data / Operating Mode - Siemens SINAMICS S120 Commissioning Manual

With startdrive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.7.2.3

Line data / operating mode

You set the most important parameters for the operation of an infeed in the function view of
the "Line data / operating mode" screen form. The corresponding parameters are displayed
depending on the infeed type.
Figure 4-72
The representation of this screen form is dependent upon the respective Line Module being
used:
Setting
Device supply
voltage
DC-link voltage
setpoint default
setting
Supply/DC-link
identification
Operating mode for
ALM
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1
Example: Network data/operating mode for Active Line Module
ALM
SLM
x
x
x
x
4.7 Basic parameterization of the drive objects
BLM
Explanation
x
x
-
x
-
The value in this field (p3510) is deter-
mined automatically from the defined
operating voltage.
x
-
If the line supply / DC-link identification
has already been performed once, then
the value is preset to "OFF".
-
-
Presetting of the operating mode is de-
pendent upon the operating voltage of
the ALM:
≤ 415 V
Mode) active
≤ 415 V
Mode) active
Commissioning
= Unregulated Udc (Active
eff
= Udc Regulated Udc (Active
eff
177