Commissioning
4.7 Basic parameterization of the drive objects
Setting the line data and operating mode
The parameters in this screen form are assigned default values when creating the device.
1. Enter a value for the device supply voltage in the "Device supply voltage" field (p0210).
2. To activate the line/DC link identification, in the drop-down list "Supply/DC link
identification", select option "On".
Selecting the operating mode for ALM
The operating mode depends on the motor voltage.
Example: The DC-link voltage must be lower in the USA. For this reason, you can switch the
mode of an Active Line Module in order to be able to use it as a Smart Line Module (Smart
Mode). You can set the operating mode in this screen form for operating voltages greater
than 415 V
1. Set one of the two operating modes:
– "Vdc non-regulated (Smart Mode)"
– "Vdc regulated (Active Mode)"
178
(ALM).
rms
In Smart Mode, the regenerative capability is maintained, but this results in a lower
DC-link voltage compared to Active Mode. The DC-link voltage depends on the
current supply voltage.
In Active Mode, the DC-link voltage is regulated to a settable setpoint (p3510) to
produce a sinusoidal supply current (cos φ = 1). The size of the reactive current is also
regulated and can be set specifically.
Commissioning with Startdrive
Commissioning Manual, 11/2017, 6SL3097-4AA10-0BP1