Commissioning
6.8 Commissioning: Basic procedure
6.8.1.3

Accepting the settings in the drive

After you have parameterized all safety functions, the drive must accept the settings.
Note
To accept the settings in the drive, it must be online.
1. To accept the settings and deactivate the safety functions, click the
The following steps are executed:
– The parameter settings are copied from CPU 1 to CPU 2.
– Copy RAM to ROM is offered.
– Safety mode is deactivated, the icon now has a yellow border.
2. Go offline with the drive.
You can now continue with the further settings of the parameterization. The dialogs are
no longer deactivated.
6.8.1.4

Changing the safety password

The safety password protects safety parameters against maloperation. Always assign a
strong password, to enable protection. To reset the password to the factory setting, you
require the valid password.
Note
The safety password does not have the equivalent quality of a password (protection against
unauthorized access, e.g. by an attacker), but rather that of write protection (e.g. protection
against maloperation).
Requirement
● The drive axis is ONLINE.
The safety password can only be read or changed in online mode.
286
"Drive axis > Parameter > Safety Integrated > Enter password"
icon in the toolbar.