Control of the safety functions
5.6 Control of the Extended/Advanced Functions via F-DI (for CU310-2)
Function diagrams (see SINAMICS S120/S150 List Manual)
• 2870
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p10002
• p10017
• p10040
• r10051.0...2
5.6.3

Function of the F-DO

Description
The failsafe digital output (F-DO) comprises 2 digital outputs plus one digital input that
checks the switching state for forced checking procedure (test stop). The 1st digital output
switches 24 V DC, and the 2nd switches M of the X130 (CU310-2) voltage supply.
The status of each F-DO can be read at parameter r10052. The status of the associated
DI22 can be read using parameter r0722.22.
The actuator connected to the F-DO can also be tested under specific conditions as part of
forced checking procedure (test stop). See Section "Forced checking procedure (test stop) of
the CU310-2 (Page 306)".
Table 5- 21
Module
CU310-2
Signal sources for the F-DO
For the CU310-2, the following signals are available for interconnecting (p10042, ..., p10045)
on the F-DO:
● STO active
● SS1 active
● SS2 active
● SOS active
● SLS active
● SSM feedback active
246
SI functions - CU310-2 (F-DI 0 ... F-DI 2)
SI Motion F-DI switchover discrepancy time (CPU 1)
SI Motion digital inputs debounce time (CPU 1)
SI Motion, F-DI input mode (CPU 1)
CO/BO: SI Motion digital inputs status (CPU 1)
Overview of the failsafe outputs in the SINAMICS S120/S150 List Manual:
Function diagram
2873
Outputs
F-DO 0
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
Associated checking
inputs
DI 22
Safety Integrated