● If the automatically initiated function cannot be correctly completed as a result of a
problem (e.g. communication failure), then after the problem has been resolved, the
function is automatically restarted.
● After the forced checking procedure (test stop) has been performed successfully, the
converter goes into the "Ready" state.
● Timer p9659 is automatically reset as a result of the forced checking procedure (test
stop).
● The automatic forced checking procedure (test stop) for POWER ON does not influence
the Safety Integrated Functions.
Note
Resetting the timer of the Basic Functions
If when simultaneously using the Extended Functions, the forced checking procedure (test
stop) is performed, then the timer of the Basic Functions is also reset.
Discrepancy is not checked at the terminals used to select the Basic Functions as long as
STO is set by the Extended Functions. This means that the forced checking procedure (test
stop) of the Basic Functions must always be performed without the selection of STO or SS1
by the Extended Functions. It is otherwise not possible to verify the correct control through
the terminals.
4.1.6

Function diagrams and parameters

Function diagrams (see SINAMICS S120/S150 List Manual)
• 2800
• 2802
• 2890
• 2891
• 2900
• 2901
• 2902
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
SI Basic Functions - Parameter manager
SI Basic Functions - Monitoring functions and faults/alarms
SI TM54F - Overview
SI TM54F - Parameter manager
SI TM54F - Basic Functions control interface (p9601.2/3 = 0, p9601.6
= 1)
SI TM54F - Basic Functions Safe State selection
SI TM54F - Basic Functions assignment (F-DO 0 ... F-DO 3)
Description of Safety Integrated functions
4.1 Safety Integrated basic functions
89