8.4 Response times
8.4.13

Advanced Functions without encoder via PROFIsafe (CU310-2 and CU320-2)

The following table lists the response times
Control Unit up to initiating the particular response.
Table 8- 13
Response times when controlling via PROFIsafe
Function
SP
2)
The specified response times involve internal SINAMICS response times. Program run times in the F-host and the
1)
transmission time via PROFIBUS or PROFINET are not taken into account. When calculating the response times be-
tween the F-CPU and the converter, you must take into account that faults in the communication can result in a safety
function only being selected after the PROFIsafe monitoring time (F_WD_Time) has expired. The PROFIsafe monitoring
time (F_WD_Time) must also be included in the calculation when an error occurs.
SP: The data corresponds to the times between acquisition of the safe position and transfer of the safe position via
2)
PROFIsafe.
370
from receiving the PROFIsafe telegram at the
1)
Drive system has no fault
6 · p9500 + p9587 + 4 ms
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
Worst case for
A fault is present
6,5 · p9500 + p9587 + 32 ms
Safety Integrated