Acceptance Test With Startdrive; Notes - Siemens SINAMICS S120 Function Manual

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Acceptance test

7.3 Acceptance test with Startdrive

7.3
Acceptance test with Startdrive
7.3.1

Notes

Note
Conditions for the acceptance test
As far as possible, the acceptance tests are to be carried out at the maximum possible
machine speed and acceleration rates to determine the maximum braking distances and
braking times that can be expected.
Note
Acceptance test for Basic and Extended Functions
In the function selection, the Safety Integrated acceptance test offers you the testable
functions for selection, depending on the device type and its settings (Basic or Extended
Functions, control via PROFIsafe or terminals).
Note
Trace recordings
The trace recordings for the Extended Functions allow the analysis of the machine behavior
during the test execution. Here you use the signal characteristics to check whether the
machine behavior meets your expectations. The recorded signals allow, for example, the
delay times and over-travel distances to be evaluated.
Note
Non-critical alarms
When evaluating the alarm buffer you can tolerate the following alarms:
• A01697 SI Motion: Motion monitoring test required
• A35014 TM54F: Test stop required
These alarms occur after every system startup and can be evaluated as non-critical.
• A01699 SI CU: Shutdown path test required
This alarm occurs after the time in p9659 has expired.
You do not need to include these alarms in the acceptance report.
Note
No acceptance test with alarm A01796
If the alarm A01796 is active, the pulses are safely canceled, and an acceptance test is not
possible.
344