Configuration
8.5 Configuration control (option handling)
Operating principle of configuration control
You can use the configuration control to operate different expansion levels of a series
machine with a single configuration of the HCS.
● A station master is configured in a project (maximum configuration). The station master
comprises all modules needed for all possible plant parts of a modular standard machine.
● The project's user program provides for several station options for various standard
machine configuration levels as well as selection of a station option. For example, a
station option uses only some of the modules of the station master.
● The standard machine manufacturer selects a station option for a configuration of the
standard machine. To do this, the project need not be modified, and it is not necessary to
load a modified configuration.
Using a custom control data record, you inform the HCS which modules in a station option
are missing or are located in a different slot as compared to the station master. The
configuration control does not have an impact on the parameter assignment of the modules.
The following figure shows 3 expansion levels of a heating control system with the
associated station options.
Figure 8-1
Advantages
● Simple project execution and commissioning by using a single STEP 7 project for all
station options.
● Easy handling during maintenance, versioning and upgrades:
● Savings potential in the creation, commissioning and the documentation for standard
machines.
Procedure
To set up the configuration control, follow these steps:
Step
116
Configuration control
Procedure
1
Enable configuration control in STEP 7
2
Create control data record
3
Transfer control data record
See section
Configuring (Page 117)
Control data record (Page 118)
Transferring the control data record in the startup
program of the CPU (Page 121)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006