System overview
3.6 Power Output Module (POM)
3.6
Power Output Module (POM)
3.6.1
POM4220
Function
The power output module (POM) offers power outputs for resistive loads and can be
operated in TN and TT networks.
POM version
POM4220 Lowend
POM4220 Midrange phase angle control
POM4220 Highend
POM4220 Flexible
You will find detailed connection information in the section "Technical specifications
(Page 205)".
26
Number of
Output voltage
power outputs
Total contact rating
16
230 V AC/ 16.1 kW
•
12
230 V AC/ 23 kW
•
277 V AC/ 27.7 kW
•
8
230 V AC/ 23 kW
•
277 V AC/ 27.7 kW
•
400 V AC/ 40 kW
•
480 V AC/ 48 kW
•
12
45 V AC/ 4.5 kW
•
70 V AC/ 7 kW
•
110 V AC/ 11 kW
•
230 V AC/ 23 kW
•
277 V AC/ 27.7 kW
•
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006