6.2
Connecting the protective conductor
Risk of electric shock
Can cause death or serious injury
• The protective conductor must be connected to the threaded pin indicated.
• HSC4200: The cable cross-section for the protective conductor must be ≥ 10 mm
• HSC4300: The cable cross-section for the protective conductor must be ≥ 16 mm
• The cable lug used must have a tin-coated surface to ensure corrosion protection.
• When connecting the protective conductor, the applicable national and local regulations
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
WARNING
must be observed.
6.2 Connecting the protective conductor