Power Supply And Distribution Requirements - Huawei FusionModule1000A20 Installation Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One Data
Center
Installation Guide
(1) Pre-fab. module base

2.3 Power Supply and Distribution Requirements

Issue 02 (2020-01-15)
Figure 2-2 Base installation scenario diagram (unit: mm)
The minimum cross-sectional area of a concrete platform must be 2900 mm x 1000 mm.
The error of the upper surface of a concrete platform must be less than 10 mm. A concrete
platform must be at least 200 mm higher than the ground.
Determine the actual height of the concrete platforms based on the local drainage and weather
conditions.
The concrete platform should have a maximum load bearing capacity of 15,000 kg and the
recommended seismic acceleration is 3 g. The specific strength is calculated based on the
contact area (a single base installed on the ground is 1720 cm
Concrete pads or passages with the load-bearing capacity meeting local civil work
standards can be built on the site outside the concrete platforms for access and servicing.
The power supply for the FusionModule1000 can be the mains or a diesel generator
(DG). For the detailed input routes and capacity, see the power supply and distribution
system diagram for the solution in use.
Copyright © Huawei Technologies Co., Ltd.
(2) Concrete platform
2 Site Requirements
(3) Ground
2
).
4