Step 4 Secure the waterproof metal connector using the dedicated feeder window wrench by
tightening the nut to a torque of 100 N· m, as shown in
Figure A-13 Securing the waterproof metal connector
Step 5 Apply transparent sealant onto the joint between the waterproof metal connector and the sheet
metal on the pre-fab. module, as shown in
Figure A-14 Applying sealant
Step 6 Spray water to test the waterproof performance of the waterproof metal connector.
----End
A.1.7 Attaching Cable Labels
Prerequisites
Preparations
Tool: pen
Issue 02 (2020-01-15)
If the cable is not regular or the size does not meet the requirements, wrap waterproof sealing tape.
Cables have been connected.
You are clear about the connections of cables to be labeled.
Clear and specific label information facilitates future pre-fab. module maintenance work.