Danger to life through interruption of the external protective conductor due to high leakage
currents
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
• Ensure that the external protective conductor satisfies at least one of the following
Danger to life through electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
• As a minimum, connect cable shields and the cores of power cables that are not used
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel through
smoke development and fire. This can also result in more downtimes and Line Modules
may have a reduced service life.
• It is absolutely essential that you maintain ventilation clearances according to the table
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of the safety
• If safe electrical separation cannot be guaranteed (for linear motors or third-party
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
WARNING
conditions:
– It has been laid so that it is protected against mechanical damage.
– If it is a single cable, it has a cross-section of at least 10 mm² Cu.
– If it is a conductor of a multi-conductor cable, it has a cross-section of at least 2.5
mm² Cu.
– It has a second protective conductor in parallel with the same cross-section.
– It complies with the local regulations for equipment with increased leakage current.
Cables laid within control cabinets or closed machine housings are considered to be
1)
adequately protected against mechanical damage.
WARNING
(e.g. brake cores) at one end at the grounded housing potential.
WARNING
Ventilation clearances above and below the component (Page 310).
WARNING
isolation.
motors, for example), use a Sensor Module External (SME120 or SME125) or Terminal
Module TM120.
Motor Modules Booksize Compact as expansion axes
6.2 Safety information