Siemens SINAMICS S120 Combi Equipment Manual page 163

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

Danger of an accident due to missing warning labels in the national language.
Missing warning labels in the national language regarding the DC link discharge time can
result in death or serious injury.
• Attach the component warning labels in the national language.
Fire hazard due to overheating because of inadequate ventilation clearances
Inadequate ventilation clearances can cause overheating with a risk for personnel due to
smoke and fire. This can also result in increased failure rates and a shorter service life for
Line Modules.
• It is absolutely essential that you maintain ventilation clearances according to the table
NOTICE
Material damage due to loose power connections
Insufficient tightening torques or vibrations can result in faulty electrical connections. This
can cause fire damage or malfunctions.
• Tighten all the DC link busbar screws with the specified tightening torques (1.8 Nm
• Check the tightening torques of all power connections at regular intervals and tighten
NOTICE
Material damage due to loose power connections when using the 24 V terminal adapter
Insufficient tightening torques or vibrations can result in faulty electrical connections. This
can cause fire damage or malfunctions.
• When using the 24 V terminal adapter, it must be screwed onto the Control Supply
• Check the tightening torques of all power connections at regular intervals and tighten
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
WARNING
WARNING
Ventilation clearances above and below the component (Page 310).
tolerance +30 %).
them when required. This applies in particular after transport.
Module Tighten the enclosed EJOT-PT screw K30 x 16 with the specified tightening
torque (0.5 Nm).
them when required. This applies in particular after transport.
DC link components
7.1 Control Supply Module CSM
163