Line-side power components
3.5 Overvoltage protection
Derating characteristics
Figure 3-3
3.5
Overvoltage protection
To protect the units against line-side surge voltages, install an overvoltage protection device
(surge arrester) directly at the infeed point. For use in Canada, to comply with the
requirements of CSA C22.2 No. 274, a UL category VZCA7 or VZCA8 surge arrester is
absolutely mandatory. The Raycap company has suitable surge arresters.
42
The rated current and tripping current depend on the ambient temperature for rated
residual currents over 100 mA
SINAMICS S120 Combi