12.9 Note on control cabinet cooling
12.9.4

Power loss of components in rated operation

12.9.4.1

General information

The tables below provide an overview of the power loss of all components during rated
operation. The characteristic values apply for the following conditions:
● Line supply voltage 400 V
● Pulse frequency of the Motor Modules 4 kHz (clock frequency of the spindle 4 kHz or 8
kHz)
● Operating components at their rated power
The total losses of the relevant components (S120 Combi, Motor Module) are calculated
from the power loss and the corresponding losses from the electronics.
12.9.4.2
Power losses for SINUMERIK control systems, DC link components and
supplementary system components
Table 12- 18 Overview of power losses at rated operation for SINUMERIK control systems, DC link
SINUMERIK 828D
SINUMERIK NCU 710.3 PN
SMC20/30
SME20/25
TM54F
Braking Module
Control Supply Module
Line
DC link
316
components and supplementary system components
Unit
W
W
W
W
W
W
W
W
Power loss
28
21
< 10
< 4
4.5
20
70
65
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5