Operating line connection components via an autotransformer

An autotransformer can be used to adapt the voltage in the range up to 3-ph. 480 V AC 10
%.
Danger to life through electric shock due to high voltage
If the voltage applied is too high for the existing insulation, there is a danger of electric
shock.
• Use an isolating transformer for voltages from 3-ph. 480 V + 10 %.
NOTICE
Damage when using an autotransformer
If an autotransformer is used, safe electrical separation is no longer possible for a line
voltage higher than 480 V +10 %. This can lead to damage or a fault in the device.
• In this case, use an isolation transformer.
62
> S
⇒ S
is decisive
n2
n1
for the matching transformer can be reduced by reducing u
WARNING
of 21 kVA for a short-circuit voltage u
n
. In the examples listed
k
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5