STOP/RUN status change function
This function changes the STOP/RUN status of the VxWorks part at an arbitrary time.
For example, the cyclic data of the CC-Link IE Field Network function can be cleared or conditional branches of user
programs can be used.
The operation status of the VxWorks part has the following types. The status can be changed at an arbitrary time when a stop
error is not occurring on this product.
• RUN
• STOP
• Changes to the STOP/RUN status of the VxWorks part do not affect the operation on the Windows part.
• To change the STOP/RUN status by a remote operation or function, change the position of the STOP/MAIN
RUN switch to 'MAIN RUN'. If the STOP/MAIN RUN switch is in the Stop position, the STOP/RUN status will
be fixed to STOP.
• After changing the STOP/RUN status to STOP by a remote operation or a function, the STOP/RUN status
will not change to RUN even if the position of the STOP/MAIN RUN switch is changed to RUN. Change the
STOP/RUN status to RUN by a remote operation or a function.
• Even when the operating status of the VxWorks part is either STOP or RUN, the data processing of a user
program is performed. To divide program processing depending on the operating status of the VxWorks
part, use the C Controller module dedicated function (CCPU_GetCpuStatus). (MELIPC MI5000 Series
Programming Manual (VxWorks))
Change of the operating status
Use one of the following methods to change the operating status.
■Switch operations
Use the STOP/MAIN RUN switch.
(MELIPC MI5000 Series User's Manual (Startup))
■remote operation
Use a remote operation of MI Configurator. ( Page 104 Remote operation function)
■C controller module dedicated function
Use the C Controller module dedicated function (CCPU_Control)
• Function list
Function name
CCPU_Control
For details on the C Controller module dedicated functions, refer to the following manual.
MELIPC MI5000 Series Programming Manual (VxWorks)
STOP/RUN status
Changes to the STOP/RUN status of the VxWorks part affect the following functions.
Function
CC-Link IE Field Network FUNCTION
CC-Link IE Field Network Basic function
• Buffer memory values are retained even when the STOP/RUN status is changed.
• If the VxWorks part is in the STOP state, writing data to the buffer memory using a C Controller dedicated
function will be disabled.
8 DIAGNOSTIC AND MAINTENANCE FUNCTIONS
102
8.3 Operating Status Management Function
Description
Performs a remote operation (remote RUN/STOP) of the MELIPC.
Description
When the status is changed to STOP, whether to clear or retain the
output of cyclic data can be selected.
Reference
Page 49 Output status when
this product is STOP
Page 88 Output status when
this product is STOP