Mitsubishi Electric MELIPC MI5000 Series User Manual page 267

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

No.
Name
SB0013
Reserved station specified enabled
request
SB0040
Own station network type
SB0043
Own station unit operation mode
SB0044
Own station settings 1
SB0046
Own station number settings status
SB0047
Baton pass status of own station
SB0049
Own station data link error status
SB004A
Own station minor error status
SB004B
Own station moderate/major error
status
SB004C
Own station operating status
SB004D
Received parameter error
SB0050
Own station link start reception status
SB0051
Own station link start end status
SB0052
Own station link stop reception status
Description
Requests enabling of the reserved station specification for the station specified by 'reserved station
temporary clear / temporary error disabled station settings' (SW0010 to SW0017). (Request possible
only for stations currently under reserved station temporary clearing)
• OFF: No request
• ON: Request
(If switched from ON to OFF, error content stored in 'Reserved station specified enabled request results'
(SW0057) is cleared.) )
Stores own station network type.
• ON: CC-Link IE Field Network
Stores own station unit operation mode.
• OFF: Online
• ON: Other than online
Stores own station type.
• OFF: Slave station (other than master station)
• ON: Master station
Stores station number settings status.
• OFF: Station number confirmed
• ON: Station number unconfirmed
When the parameter was set in MI Configurator, always OFF.
Stores baton pass status of own station (transit transmission enabled).
• OFF: Normal
• ON: Error
In the event of an error, the cause of the error can be confirmed by using the 'baton pass status of own
station' (SW0047) and 'cause for baton pass interruption' (SW0048).
Stores own station data link error status.
• OFF: Normal
• ON: Error
In the event of an error, the cause of the error can be confirmed with 'data link stop factors' (SW0049).
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
The minor error occurrence status of own station is stored.
• Off: No minor error
• ON: Minor error
The moderate/major error occurrence status of own station is stored.
• OFF: No moderate or major error
• ON: Moderate or major error
The operating status of own station is stored.
• OFF: RUN
• ON: STOP, moderate or major error
The received parameter status is stored. (In the case of a master station, its parameter status)
• OFF: Normal
• ON: Error
Stores 'own station link start' (SB0000) reception status.
• OFF: Not received (SB0000 OFF)
• ON: Received (SB0000 is ON)
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
Stores link start processing status from 'own station link start' (SB0000).
• OFF: Link start not ended (SB0000, SB0050 OFF)
• ON: Link start ended (SB0000, SB0050 ON)
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
The reception status of own station link stop (SB0001) is stored.
• OFF: Not received (SB0001 OFF)
• ON: Received (SB0001 ON)
<Conditions>
Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
Appendix 7 List of Link Special Relays
A
APPX
265