File/folder access not possible
Check the following items.
Check item
There is no free space in the write target drive.
Are there any applications (including user programs) using the corresponding
files?
Is the network under high load?
Are high priority programs running?
Is the VxWorks part system drive being written to?
Is the Windows part system drive being written to?
When accessing the files (writing, reading, etc.), is the STORAGE LED
flashing?
Was the CFast card removed while the power supply of this product was ON?
*1 The standard drives of this product are listed below.
Windows part: system drive (C:\)
VxWorks part: system drive (/SYSTEMROM), user drive (/ROM)
Has hardware diagnoses completed?
Check the following items.
Check item
Are all LEDs off?
Does the MAIN RUN LED turn on, and is the dot matrix LED display updated?
Is the MAIN ERR LED flashing with no text displayed on the dot matrix LED?
Is the LED status different than that detailed in the hardware diagnostic
function?
Windows recovery does not complete
Check the following items.
Check item
Is 'Ready' or 'Running' displayed on the dot matrix LED?
Is the LED status different than that detailed in Windows recovery?
APPX
208
Appendix 1 Troubleshooting by Symptom
Corrective action
• Delete files on the write drive to create free space.
• Change the write target to another drive.
• Close the applications using the corresponding files.
• Add exclusive control of file access to a user program that accesses the
corresponding files.
• Consult with the administrator of the connected LAN and disconnect
devices connected by Ethernet that may cause a high load.
• Change the connection of the personal computer and this product to a
different network.
• Wait until the operation of the high priority program is completed.
• Ensure that high priority programs are not run.
Change the write-target drive.
Disable the Unified Write Filter before writing.
• If the access target is not the standard drive
wiring. If there are no problems with the wiring, check the manual of the
device being used.
• If the access target is the standard drive
a hardware fault of this product. Consult your local Mitsubishi
representative.
Turn the product OFF, insert the CFast card, and then turn the product ON
again.
Corrective action
Run hardware diagnoses again. If the problem is not resolved, initialize this
product.
If initialization is not completed or the issue remains after initialization, this
may indicate a hardware fault. Consult your local Mitsubishi representative.
Corrective action
If the STORAGE LED does not flash for a long time, perform Windows
recovery again.
If the same issue remains after recovery, this may indicate a hardware fault.
Consult your local Mitsubishi representative.