Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 283

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

No.
Name
SW01C0
Each station CC-Link IE Field Network
to
synchronous communication function
SW01C7
information
SW01C8
Each station synchronized/not
to
synchronized operation status
SW01CF
information
SW01E9
Synchronous communication cycle
overrun count
SW01EA
Synchronous communication cycle
settings value
SW01EB
Description
Stores supported/not supported for each station CC-Link IE Field Network synchronous
communication function settings status.
• 0: Not supported
• 1: Supported
The numbers within the following illustration indicate the station numbers. (: fixed at 0)
b15
SW01C0
16 15 14 13 12
SW01C1
32 31 30 29 28
SW01C6
112 111 110 109 108
SW01C7
-
-
-
-
-
<Conditions>
• Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
• Only enabled for stations with normal 'each station baton pass status' (SW00A0 to SW00A7).
• The status is not stored for the station numbers after the maximum station number.
Stores each station CC-Link IE Field Network synchronous communication function operational
status.
• 0: Not synchronized
• 1: Synchronized
The numbers within the following illustration indicate the station numbers. (: fixed at 0)
b15
SW01C8
16 15 14 13 12
SW01C9
32 31 30 29 28
SW01CE
112 111 110 109 108
SW01CF
-
-
-
-
-
<Conditions>
• Enabled when 'baton pass status' of own station (SB0047) is OFF. When 'baton pass status of own
station' (SB0047) is ON (error), the data immediately before is retained.
• Stations that have not run an inter-module synchronous interrupt program because the CPU
operating status is STOP or similar are also not synchronized (0).
• Only enabled for stations with normal 'each station baton pass status' (SW00A0 to SW00A7).
• The status is not stored for the station numbers after the maximum station number.
Shows the count for when link scan does not complete within the synchronous communication cycle.
Clear by turning the power supply OFF to ON, or clearing the reset state.
• 0: No cycle overrun event
• 1 to 65535: Accumulated number of cycle overrun events
Stores the synchronous communication cycle settings value. (Units: μs)
b0
~
5
4
3
2
1
~
21 20 19 18 17
~
~
102 101 100 98 97
~
117 116 115 114 113
b0
~
5
4
3
2
1
~
21 20 19 18 17
~
~
102 101 100 98 97
~
117 116 115 114 113
Appendix 8 List of Link Special Registers