Error messages via the "error_code" variable
Error Code
(B#16#..)
A0 03
Illegal receiver identifier
S
System error. Cannot occur with FC 56 (see telegram layout in chapter B.3)
A0 06
The started command is not permitted (not defined). Correct the "command" parameter
in the UDT 50 call (see chapter 4.1).
A0 11
The telegram check parameters (DBN or command) are not coming in the correct order.
Two or more telegrams have been written to the same ASM.
S
Check the parameterization of the parameters ASM_address and ASM_channel in
MOBY DB-FH.
S
Do not execute command start with "control variable" function.
A0 16
The filehandler is currently processing another command. Execution of a RESET
command is mandatory.
A0 17
The data block of the SLG is too long and cannot be transferred with PROFIBUS.
S
The "block length" parameter for the RESET command is too long (FC error or user
error).
S
Program sequence error on the SLG
S
Perform new start of the ASM and start command again.
A0 18
Communication error. MOBY driver is active while a new command is being sent.
S
Check command sequences in the application.
S
Perform new start of the ASM.
B0 01
Fault in connection to the SLG.
S
Cable between ASM and SLG is incorrectly wired or cable is damaged.
S
24 V supply is not connected or is switched off.
S
Automatic fuse on the ASM has blown.
S
Hardware defect
This error is not indicated for the start of the system commands (RESET, NEXT,
ASM/SLG-STATUS).