The Parameter Data Block
Table 3-2
INPUT-Parameter
Variable
distance_limiting
MOBY U: Working range restriction
multitag
Maximum number of MDSs being processed in parallel in the field
MOBY I:
MOBY U:
field_ON_control
MOBY U: Proximity switch mode; switch antenna field on/off automatically.
field_ON_time
MOBY U: Time for proximity switch mode (field_ON_control = 02)
3-6
05 hex
=
0.5 m
0A hex
=
1.0 m
0F hex
=
1.5 m
14 hex
=
2.0 m
19 hex
=
2.5 m
1E hex
=
3.0 m
23 hex
=
3.5 m
Permissible value = 1
Permissible values = 1 to 12
The command "antenna ON/OFF" is suppressed
in proximity switch mode.
00 hex
= No proximity switches
01 hex
= One or two proximity switches.
The proximity switches have a logical OR link.
During the time a proximity switch is activated, the
field is turned on.
02 hex
= One or two proximity switches.
The 1st proximity switch turns on the field
while the 2nd proximity switch turns off the field.
When two proximity switches exist and a
field_ON_time is parameterized, the field is
automatically turned off if the 2nd proximity switch
doesn't react within this prox. switch time.
If no field_ON_time is parameterized, the field
remains on until the 2nd prox. switch is activated.
00 hex
= Time monitoring is off. The 2nd prox. switch is
needed to turn off the field.
01 hex to FF hex = 1 to 255 sec. Turn on time for the SLG field.