Siemens MOBY FC 56 Technical Description page 106

Table of Contents

Advertisement

Error Messages and Trouble-Shooting
Table 9-2
Error messages via the "error_code" variable
Error Code
(B#16#..)
C0 17
The filehandler is not working correctly.
S
Check command format and command sequence.
S
The ASM hardware (firmware) is defective.
C0 18
Operating system error (AMOS mailbox)
S
Perform init_run of the ASM.
C0 19
The number of MDSs in the field is greater than the number of MDSs parameterized in
"multitag."
S
Remove excess MDSs from the field.
S
Configuration of distance_limiting is set incorrectly.
S
Search the surroundings of the SLG for an MDS that is located in the field by
coincidence.
S
Only one MDS can be processed with MOBY I.
C0 20
Communication error between filehandler and MDS driver. The MOBY driver doesn't
recognize the command from the filehandler.
S
Perform init_run of the ASM.
C0 21
Operating system error. Watchdog error on ASM/SLG.
S
Perform init_run of the ASM.
D0 01
The filehandler will only accept RESET commands.
S
The filehandler has not yet been initialized by an init_run.
S
This situation can only be remedied by an init_run.
D0 05
The FORMAT, CREATE, WRITE, ATTRIB, UPDATE, COVER, QUEUE READ or
QUEUE WRITE commands have been issued with incorrect parameters
S
FORMAT with invalid MDS name or MDS type
S
CREATE with invalid file name
S
WRITE/UPDATE with length 0 (DLNG = 0)
S
Attribute not permissible
S
QUEUE WRITE or QUEUE READ with invalid option or number of files
S
COVER with invalid user (only 0 or 1 permissible)
S
D0 07
The system data transmitted with the LOAD command is incorrect.
– DLNG parameters incorrect with LOAD (see section 4.2).
– Data block given is incorrect or has incorrect parameters
(see section 4.2).
– MOVE command executed incorrectly. DIR + FAT on MDS don't correspond to
the checksum.
S
The MOVE command cannot be executed. The checksum does not correspond to
DIR + FAT. The MDS has apparently left the transmission window while system
operations were being performed (e.g. write DIR + FAT).
S
MOBY U: The LOAD and MOVE commands are not supported.
D0 09
An init_run command has been issued by the FC 56 with invalid parameters. Cause of
fault lies in user program.
S
Check the INPUT parameters of the UDT 10 call (address 8 to 17 in UDT 10, see
chapter 3.1)
9-6
Description
J31069-D0155-U001-A0-7618
FC 56

Advertisement

Table of Contents
loading

Table of Contents