Application Environment - Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)

3.3.3.2 Application Environment

Table 3-32 lists the environmental specifications. Table 3-33 lists the physical ports. Table
3-34 lists the installation requirements. Table 3-35 lists the water quality requirements.
Environmental Specifications
Table 3-32 Environmental specifications
Item
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Outdoor temperature
Protection level
Altitude
Issue 04 (2017-06-30)
The filter dryer absorbs moisture from refrigerant pipes and filters out foreign matter,
which reduces the component damage probability and ensures efficient and reliable
operating of components.
Sight glass
The sight glass allows you to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
Electric heater
The Positive Temperature Coefficient (PTC) electric heater features quick start, large
heating capacity, and balanced heat dissipation and provides multiple protection
mechanisms to ensure the secure and stable running of the equipment.
Electrode humidifier
The electrode humidifier provides stepless adjustment of humidification capacity and
precise control of indoor humidity.
Water pump
The water pump provides power for top drainage with a maximum lift of 4 meters.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
18–45° C
20%–80% RH
–40° C to +70° C
5%–95% RH (non–condensing)
Working with the NetCol500–A032 (including
low–temperature components): –40° C to +45° C
Working with the NetCol500–A036: –20° C to +55° C
Working with the NetCol500-A026SC11E0: –20° C to
+45° C
Working with the NetCol500-A0265S11E0: –20° C to
+55° C
Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40° C to +45° C
Indoor unit: IP20
Outdoor unit: IPX5
0–1000 m. When the altitude is greater than 1000 meters, the
cooling capacity is derated. The maximum operating altitude is
4000 meters. For the detailed derated data, contact Huawei
technical support