Huawei FusionModule2000 Product Description page 39

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
circuit breakers for
IT equipment
Dimensions (H x
W x D)
An integrated UPS cabinet works when the input power is 380 V, 400 V, or 415 V, and
features redundancy, high reliability, high efficiency, environment friendliness, high flexibility,
and intelligent and simple operations.
Table 3-8 lists the technical specifications of an integrated UPS cabinet.
Table 3-8 Technical specifications of an integrated UPS cabinet
Category
Input
Output
Issue 04 (2017-06-30)
63 A/1P x 6 x 2
2000 mm x 600 mm x 1100 mm
2000 mm x 600 mm x 1200 mm (with a tail frame)
2200 mm x 600 mm x 1200 mm (with a top frame and tail frame)
Item
Input system
Rated input voltage
Input voltage range
Input frequency range
Input power factor
Rated input current
Output system
Voltage
Frequency
Output PF
Transfer time
Output voltage
unbalance
Overload capability
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Specifications
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (line
voltage)
80–280 V AC (phase voltage) (When the input
voltage ranges from 80 V AC to 176 V AC,
loads are linearly derated.)
40–70 Hz
0.99 (full load); 0.98 (half load)
Air-cooled 1: 250 A; air-cooled 2: 400 A;
air-cooled 3: 125 A
Three-phase, four-wire, PE wire
380 V AC, 400 V AC, or 415 V AC (tolerance
± 1%) (line voltage)
In normal mode, the mains frequency is
synchronized with the bypass input frequency.
In battery mode, the frequency is 50 Hz or 60
Hz (tolerance ± 0.25%).
1
0 ms (Normal)
Voltage unbalance: ± 3%; phase unbalance: ± 2°
Inverter overload capability:
105% < load ≤ 110%: transfer to bypass
mode after 60 min
110% < load ≤ 125%: transfer to bypass
mode after 10 min
3 System Architecture
63 A/1P x 6
32