Huawei FusionModule2000 Product Description page 77

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description (380 V)
Table 3-41 Installation requirements
Parameter
Installation mode
Pipe and cable
routing
Room door
Floor
Equivalent length of
the one-way pipeline
Height difference
between the indoor
and outdoor units
Water supply
requirements
Drainage
requirements
Power distribution
requirements
Note: If the requirements are not met, contact Huawei technical support for an optimized
plan.
Water Quality Requirements
Issue 04 (2017-06-30)
Description
Installed on a concrete floor or an ESD floor
Pipes and cables can be routed from the top or bottom. The
automatic drainpipes can only be routed from the bottom.
Width ≥ 0.9 m; height ≥ 2.3 m
Bearing capacity ≥ 350 kg/m
≤ 60 m
If the outdoor unit is placed higher than the indoor unit, the
maximum vertical distance between them should be less than or
equal to 20 meters.
If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them should be less than or
equal to 5 meters.
The water supply pressure ranges from 0.1 MPa to 0.7 MPa.
The water supply temperature ranges from 1° C to 40° C.
The water supply instantaneous flow should be greater than or
equal to 0.6 L/min.
The water quality must meet the requirements listed in Table
3-42.
The distance between the upper drainage of the water pump and
the cabinet installation floor should be less than 3.5 m.
Drainpipe inner diameter ≥ 19 mm, automatic drainage leveling
tube length ≤ 2 m
Drainpipes should be able to withstand a temperature greater
than 85º C (for equipment configured with a humidifier).
Earth leakage circuit breakers are not recommended for mains. If
they are required by the customer or based on local regulations, use
residual current circuit breakers (RCCBs) that are not sensitive to
the single-phase DC pulse and transient current pulse.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3 System Architecture
2
; height of the raised floor ≥ 0.25 m
70